Loading...
HomeMy WebLinkAboutCity Council Ordinance 1979-06CITY OF PLYMOUTH ORDINANCE NO. 79-6 AN ORDINANCE RELATING TO THE FIRE PREVENTION CODE: AMENDING SECTION 905.05 AND 905.07 OF THE CITY CODE THE CITY COUNCIL OF THE CITY OF PLYMOUTH ORDAINS: Section 1. Section 905.05 of the City Code is hereby amended to read as follows: 905.05. Placement. Use and Maintenance of Fire Hydrants on Industrial, Commercial or Multi -Residential Property. j Installation of fire hydrants shall be required on all property zoned industrial, commercial and multiple residential uses. The number and location of fire hydrants shall be determined in accordance with the Uniform Fire Code, and with related sections of the National Fire Code published by the National Fire Protection Association re- ferenced therein, subject to the following: (a) There shall be fire hydrants placed at 300 -foot intervals along the street right-of-way; (b) Additional hydrants shall be located in such a manner that the maximum length of hoseline from any hydrant shall be 300 -feet; provided, however, that upon approval of fire protection plans and certified fire flow date, the Fire Chief may authorize a maximum hose line length of up to 500 -feet. Duly authorized officers of the City may enter upon private property for the purpose of operating and maintaining fire hydrants. Fire hydrants shall be inspected annually by the City, and an annual in- spection fee established by the City Council shall be charged for this service.